Tuff Span 6.5 and
8.0 profile roof decks are designed to replace traditional metal, wood,
and concrete decks as a substrate for built-up and single ply roofing
membranes.
These decks, like all Tuff Span panels and decks, are made with continuous
straight aligned reinforcing glass. The Tuff Span reinforcement system
allows these FRP decks to perform as a permanent substrate without the
creep problems associated with other glass reinforcing systems.
The load/span tables shown on the previous page are based upon full scale
tests. The loads shown reflect actual deck performance under dead, live,
and uplift loads.
Load Definitions
- Dead load : material
load only
- Live load : service
loads, foot traffic, etc.
- Uplift load : uplift
wind pressure minus dead load.
|
|
|
| |
PARAMETERS
AND PROPERTIES
|
|
| |
6.5
Deck Series 500 |
8.0
Deck Series 700 |
| Moment
Capacity/ft. |
11,100
lb. in. |
12,400
lb. in. |
| Stiffness
El/ft. |
2.32
x 1,000,000 lb. inches squared |
5.85
x 1,000,000 lb. inches squared |
| Fastener
Pullover |
580
lb./festener (.729" washer) |
850
lb./fastener (1.125" washer) |
| Nominal
Thickness |
0.85" |
.10" |
| Weight/SF |
1.0
lb. |
1.375
lb. |
| Flexural
Strength / ASTM D-790 |
55,000
psi |
55,000
psi |
| Flexural
Modulus / ASTM D-790 |
2.4
x 1,000,000 psi |
2.4
x 1,000,000 psi |
| Tensile
Strength / ASTM D-790 |
42,000
psi |
42,000
psi |
| Shear
Strength / ASTM D-732 |
4,500
psi |
4,500
psi |
| Barcol
Hardness / ASTM D-2583 |
50 |
50 |
| Coeeficient
of Thermal Expansion / ASTM D-696 |
8
X 1,000,000 in/in°F |
8
X 1,000,000 in/in°F |
|
|
|
| |
| FM
APPROVALS WINDSTORM CLASSIFICATIONS (See
Note 1) |
|
|
| |
6.5
Deck Series 500 |
8.0
Deck Series 700 |
| FM
Windstorm Classification |
Class
90 |
Class
90 |
| Maximum
Span |
6'3" |
8'0" |
| Deflection
Limit |
L/240
(See Note 2) |
L/240
(See Note 2) |
| Structural
Fastener Spacing |
6.5"
o.c. at every support |
8"
o.c. at every support |
| Side
Lap Fastener Spacing |
18"
o.c. |
24"
o.c. |
| Structural
Fasteners, Type B #14 |
.729"
dia., 21 ga. SS Washer |
1.125"
dia., 18 ga. Hex Head Washer |
| N-C
Insulation Fasteners |
18
Fasteners per 4' x 8' Board or 1 per 1.78 SF |
| Insulation |
Rigid
Polyiso Board, 1.3" Min. Thickness |
| BUR
Glass Felt |
3
Ply Minimum |
|
|
| Windstorm
Classification Notes: |
| 1)
Assemblies are Specification Tested per FM Approvals Simulated Wind Uplift
Test Procedure, Standard 4450. |
| 2)
Deflection limit is L/240 under a 300 lb. concentrated load on a 1 SF area
at midspan per Standard 4451. |
| |
| 6.5
Series 500 and 8.0 Series 700 decks also have U.L. Class 90 Wind Uplift
listings. |
| |
| Fire
Classification Notes: |
| 1)
Automatic sprinklers are required for Class 2 decks. |
| 2)
A roof assembly with Tuff Span 6.5 deck has obtained FM Approval for Class
1 Fire and Class 1-90 Windstorm Classification. See the current edition
of the FM Approvals Guide or contact Enduro Systems for approved assembly
construction. |
|
|
| |
|
|
|
|
Part 1 - General
Tuff Span products establish a minimum of quality required.
Part 2 - Products
Roof deck units shall be Tuff Span in one of the following profiles:
Tuff Span 6.5 Roof
Deck, Series 500
Tuff Span 8.0 Roof
Deck, Series 700.
2.01 Glass
fiber reinforcement shall be continuous and oriented in two (2) directions
(along the length and width of unit). Each unit shall be a minimum of
47% glass by weight.
2.02 Units shall be made from Vinyl Ester resins, and shall have
a flame spread rating of 25 or less when tested in accordance with ASTM
E-84.
2.03 Structural Parameters Roof deck units shall meet the specified
spans and positive and negative load capacities. Performance criteria
shall be determined by full-scale tests which represent combined stress
and elastic stability conditions. The following design criteria and Factors
of Safety (FOS) shall be analyzed and met:
Deflection (max.)
under dead loads = L/360, FOS = 5;
Deflection (max.)
under dead + temporary loads = L/240, FOS = 2.5;
Deflection (max)
under wind uplift loads (= wind uplift-dead loads) = L/180, FOS = 1.88.
Fastener pullover
minimums must account for combined stresses from the hole and from the
fastener itself.
Part 3 - Execution
3.01 Installation of Insulation Materials
3.02.01 Rigid insulation material may be attached to the FRP roof
deck units with mechanical fasteners or hot bituminous roofing adhesives
("hot mopped").
3.02.02 Mechanical fasteners must be "positive lock"
type - no screws are allowed. Contact Enduro for recommended fasteners
and fastening procedures.
3.02.03 Care must be taken when using hot roofing adhesives on
FRP roof deck units. Temperature of adhesives should not exceed the maximum
values set by the National Roofing Contractors Association (Hark 1989).
|
|
|
|
|
|