Specification:
Fiberglass Reinforced Plastic Roofing and Siding Panels
Part 1 – General
1.01 Description of Work
The scope of this specification shall include roof and/or wall units and required accessories as shown on the drawings. This shall include but not be limited to:
A. Fiberglass Reinforced Plastic (FRP) roofing and siding panels
B. FRP trim and flashing
C. Fasteners to secure panels and flashing
D. Closures and sealants
1.02 Quality Assurance
A. Materials shall comply with Federal and Local laws or ordinances, applicable codes, standards, regulations and/or regulatory agency requirements, including:
1. ASTM E72, Strength of Panels for Building Construction
2. ASTM E84, Surface Burning Characteristics of Building Materials
3. ASTM D696, Coefficient of Linear Thermal Expansion of Plastics
4. ASTM 2583, Indentation Hardness of Plastics
5. ASTM D1494, Diffused Light Transmission (translucent materials only)
6. FM 4880, FMRC Corner Fire Test (FM Approval requirement only)
B. Roofing and siding panels shall meet the performance and design criteria listed herein for the spans indicated on the drawings. Compliance with criteria shall be established by large-scale vacuum box testing for positive and negative loads as established by governing building code.
1.03 Design Criteria
A. Design Loads (Uniform Load: lbs. per square foot)
Roofing:_____ Positive _____ Negative Wind _____ Live
Siding: _____ Positive _____ Negative Wind
B. Deflection Limit
Roofing: L/D = _____
Siding: L/D = _____
C. Factors of Safety
Roofing: Positive F.O.S. = 2.5 Negative F.O.S. = 1.88
Siding: Positive F.O.S. = 1.88 Negative F.O.S. = 1.88
1.04 Submittals
Submittals shall include, but not be limited to:
A. Complete list and description of materials to be furnished
B. Product literature
C. Technical data demonstrating compliance with specified design criteria
D. Layout drawings (if required) for review and approval
Part 2 – Products
2.01 Manufacturers
Roofing and siding units shall be Tuff Span as manufactured by Enduro, 16602 Central Green Blvd., Houston, Texas 77032 (www.endurocomposites.com) or approved equal.
2.02 Materials
A. Roof and siding units shall conform to these specifications:
1. Profile/Series shall be_____________________.
2. Resin type shall be premium grade (check one):
_____ Isophthalic Polyester, UV stabilized
_____ Vinyl Ester, UV stabilized
3. Glass Fiber Reinforcements shall be continuous, straight and bi-directional (along the length and width of unit). Glass content shall be minimum of 47% by weight (30% for FM Approved materials).
4. Materials shall be fire retardant with:
_____ UL Class 1 Flame Spread Rating (25 or less per ASTM E-84).
_____ FM Approval per Standard 4880
5. Panel materials shall be protected from UV rays by:
_____ UV stabilized resin system with neopentyl glycol and acrylic monomer.
_____ UV acrylic polymer coating protection, factory-applied with minimum .4 mil dry film thickness.
_____ Surfacing mat or veil.
_____ Embossed resin-rich surface.
6. Finish shall be embossed top, smooth bottom.
7. Color shall be Enduro standard or as selected by owner.
8. Diffused light transmission (if applicable) shall be _____% per ASTM D 1494.
B. FRP Flashing and Trim
Materials shall be of thickness, dimensions, and profile required for a complete installation as shown on the drawings.
C. Fasteners
1. Structural fasteners shall be stainless steel (300 series) with sealing washers, spaced and installed per manufacturer’s recommendations.
2. Panel side lap fasteners shall be stainless steel (300 series) SB2 grommets spaced and installed per manufacturer’s recommendations.
D. Closures and Sealants
1. Sealant tape for roofing side and end laps shall be 3/32 in. thick x ½ in. wide, non- shrink/non-hardening butyl tape.
2. EPDM closures shall match unit profile.
3. Sealant for translucent panels shall be Silglaze II SCS 2800, Translucent Color by GE Silicon.
Part 3 - Execution
3.01 Handling and Storage
A. Material Handling
Protect surface of FRP panels from cuts, gouges, abrasions, and impacts. Use spreader bars when lifting FRP. Do not use wire slings unless panels are protected.
B. Storage
Protect bundled panels against standing water on top of and between sheets. Keep bundled panels under cover (but ventilated) and dry. Keep bundled panels off the ground for air circulation and with one end elevated to permit water drainage.
3.02 Installation of FRP Panels
A. Installer must follow Manufacturer’s Installation Instructions and Layout Drawings.
1. For each Type A or B stainless steel self-tapping screw, a pilot hole must be drilled through the panel and structural support. For each SB2 Grommet fastener used for side lap and flashing attachment, a pilot hole is required through the panels or flashing.
a. For drilling pilot holes use a sharp carbide-tipped sheeter’s bit and a drill speed of 500 RPM or less to avoid thread rolling.
b. For the correct Drill Bit size refer to the Drill Bit Selection Chart in the Installation Instructions.
Pilot holes are not required for self-drilling stainless steel screws, which are suitable for fastening panels to steel supports with thickness of 14 gage to ¼” (6 mm).
2. End laps shall be 6 inches minimum for roofing panels and 4 inches minimum for siding panels.
Fiberglass Reinforced Plastic Roofing and Siding Panels
Part 1 – General
1.01 Description of Work
The scope of this specification shall include roof and/or wall units and required accessories as shown on the drawings. This shall include but not be limited to:
A. Fiberglass Reinforced Plastic (FRP) roofing and siding panels
B. FRP trim and flashing
C. Fasteners to secure panels and flashing
D. Closures and sealants
1.02 Quality Assurance
A. Materials shall comply with Federal and Local laws or ordinances, applicable codes, standards, regulations and/or regulatory agency requirements, including:
1. ASTM E72, Strength of Panels for Building Construction
2. ASTM E84, Surface Burning Characteristics of Building Materials
3. ASTM D696, Coefficient of Linear Thermal Expansion of Plastics
4. ASTM 2583, Indentation Hardness of Plastics
5. ASTM D1494, Diffused Light Transmission (translucent materials only)
6. FM 4880, FMRC Corner Fire Test (FM Approval requirement only)
B. Roofing and siding panels shall meet the performance and design criteria listed herein for the spans indicated on the drawings. Compliance with criteria shall be established by large-scale vacuum box testing for positive and negative loads as established by governing building code.
1.03 Design Criteria
A. Design Loads (Uniform Load: lbs. per square foot)
Roofing:_____ Positive _____ Negative Wind _____ Live
Siding: _____ Positive _____ Negative Wind
B. Deflection Limit
Roofing: L/D = _____
Siding: L/D = _____
C. Factors of Safety
Roofing: Positive F.O.S. = 2.5 Negative F.O.S. = 1.88
Siding: Positive F.O.S. = 1.88 Negative F.O.S. = 1.88
1.04 Submittals
Submittals shall include, but not be limited to:
A. Complete list and description of materials to be furnished
B. Product literature
C. Technical data demonstrating compliance with specified design criteria
D. Layout drawings (if required) for review and approval
Part 2 – Products
2.01 Manufacturers
Roofing and siding units shall be Tuff Span as manufactured by Enduro, 16602 Central Green Blvd., Houston, Texas 77032 (www.endurocomposites.com) or approved equal.
2.02 Materials
A. Roof and siding units shall conform to these specifications:
1. Profile/Series shall be_____________________.
2. Resin type shall be premium grade (check one):
_____ Isophthalic Polyester, UV stabilized
_____ Vinyl Ester, UV stabilized
3. Glass Fiber Reinforcements shall be continuous, straight and bi-directional (along the length and width of unit). Glass content shall be minimum of 47% by weight (30% for FM Approved materials).
4. Materials shall be fire retardant with:
_____ UL Class 1 Flame Spread Rating (25 or less per ASTM E-84).
_____ FM Approval per Standard 4880
5. Panel materials shall be protected from UV rays by:
_____ UV stabilized resin system with neopentyl glycol and acrylic monomer.
_____ UV acrylic polymer coating protection, factory-applied with minimum .4 mil dry film thickness.
_____ Surfacing mat or veil.
_____ Embossed resin-rich surface.
6. Finish shall be embossed top, smooth bottom.
7. Color shall be Enduro standard or as selected by owner.
8. Diffused light transmission (if applicable) shall be _____% per ASTM D 1494.
B. FRP Flashing and Trim
Materials shall be of thickness, dimensions, and profile required for a complete installation as shown on the drawings.
C. Fasteners
1. Structural fasteners shall be stainless steel (300 series) with sealing washers, spaced and installed per manufacturer’s recommendations.
2. Panel side lap fasteners shall be stainless steel (300 series) SB2 grommets spaced and installed per manufacturer’s recommendations.
D. Closures and Sealants
1. Sealant tape for roofing side and end laps shall be 3/32 in. thick x ½ in. wide, non- shrink/non-hardening butyl tape.
2. EPDM closures shall match unit profile.
3. Sealant for translucent panels shall be Silglaze II SCS 2800, Translucent Color by GE Silicon.
Part 3 - Execution
3.01 Handling and Storage
A. Material Handling
Protect surface of FRP panels from cuts, gouges, abrasions, and impacts. Use spreader bars when lifting FRP. Do not use wire slings unless panels are protected.
B. Storage
Protect bundled panels against standing water on top of and between sheets. Keep bundled panels under cover (but ventilated) and dry. Keep bundled panels off the ground for air circulation and with one end elevated to permit water drainage.
3.02 Installation of FRP Panels
A. Installer must follow Manufacturer’s Installation Instructions and Layout Drawings.
1. For each Type A or B stainless steel self-tapping screw, a pilot hole must be drilled through the panel and structural support. For each SB2 Grommet fastener used for side lap and flashing attachment, a pilot hole is required through the panels or flashing.
a. For drilling pilot holes use a sharp carbide-tipped sheeter’s bit and a drill speed of 500 RPM or less to avoid thread rolling.
b. For the correct Drill Bit size refer to the Drill Bit Selection Chart in the Installation Instructions.
Pilot holes are not required for self-drilling stainless steel screws, which are suitable for fastening panels to steel supports with thickness of 14 gage to ¼” (6 mm).
2. End laps shall be 6 inches minimum for roofing panels and 4 inches minimum for siding panels.